@bonmj Avatar @bonmj Bon Mj

Bon Mj posts on YouTube about bon, $6367t, brand, model the most. They currently have [------] followers and [---] posts still getting attention that total [-----] engagements in the last [--] hours.

Engagements: [-----] #

Engagements Line Chart

Mentions: [--] #

Mentions Line Chart

Followers: [------] #

Followers Line Chart

CreatorRank: [---------] #

CreatorRank Line Chart

Social Influence

Social category influence automotive brands technology brands social networks currencies

Social topic influence bon #440, $6367t #50, brand, model, error #908, how to, air, mitsubishi, $8306t, $8058t

Top Social Posts

Top posts by engagements in the last [--] hours

"How to troubleshooting an Fujitsu DC inverter AC 5HP Error [--] Brand : Fujitsu DC inverter model : AOAG45LBTA ERROR : indoor error [--] #bonmj #airconditioner #fujitsu"
YouTube Link 2023-02-04T09:07Z 35.4K followers, 40.6K engagements

"Tips Fujitsu troubleshooting single split inverter air conditioner AOAG24/30JFTB Brand : Fujitsu single split inverter Model : AOAG24/30JFTB Tips for cu thermistor reading the ambient temperature is around 32c #airconditioner #bonmj #fujitsu"
YouTube Link 2023-06-10T09:12Z 35.4K followers, [----] engagements

"How to service a Daikin i-smile wallmounted air conditioner R32 Brand : Daikin i-Smile model : CTKM25VVMG/CTKMS35VVMG(FCU) model : MKM85VVMG (Outdoor) Refrigerant type : R32 How to service an aircon. Care and clean 1)Operate the fan mode for several hours on a fine day to dry out the inside. 2)After operation stops turn off the circuit breaker for the room air conditioner. 3)Clean the air filter and reattach them. 4)To prevent battery leakage take out the batteries from the remote controller. Replace dust collection filters(PM 2.5). 1)Do not wash the filters as this will reduce their"
YouTube Link 2021-10-27T15:40Z 35.4K followers, 328.2K engagements

"Daikin VRV [--] Malfunction Code List Brand : Daikin VRV [--] #bonmj #airconditioner #daikin"
YouTube Link 2025-12-28T07:09Z 35.4K followers, [----] engagements

"Daikin VRV4 how to Test run and Auto Charge. Pls note. Must do the Auto charge before test running aircon. If set to Test Run before Auto chargeerror will appear. (error-U3) #Daikin #VRV4 #bonmj"
YouTube Link 2020-12-05T18:24Z 35.4K followers, 127.4K engagements

"How to solve newly installed VRV air conditioner is showing an error HVAC Brand : Daikin VRV4 Model : RXQ20AYM Error : F4-02/F4-04 Cause : EEV coil not functioning well Action : replaced EEV coil #bonmj #airconditioner #hvac"
YouTube Link 2025-02-15T07:25Z 35.4K followers, [----] engagements

"Daikin VRV6 Automatic refrigerant charge WITH test run procedure 2-3=2* Brand : Daikin VRV [--] Model : RXUQ8B Automatic charge and test run precedure #bonmj #airconditioner #daikin"
YouTube Link 2025-12-13T12:22Z 35.4K followers, [----] engagements

"How to solve Midea air conditioner error EL-01 Model : MSEOD-18 Error : EL-01 Cause : communication issues Action : reset system (off power supply and on back) Midea AC error EL-OC R32 Single split https://youtu.be/s73fWcSuXYc #bonmj #airconditioner #midea"
YouTube Link 2025-11-23T06:21Z 35.4K followers, [----] engagements

"All you need to know about Test run Daikin VRV4 Brand : Daikin VRV [--] Model : RXQ20AYM Testing and commissioning #bonmj #airconditioner #daikin"
YouTube Link 2025-03-08T06:12Z 35.4K followers, [----] engagements

"How to solve error code F4 Wet Alarm Daikin VRV4 Brand : Daikin model : RXQ8AYM (CU) model : FXMQ140PAVE (FCU) Symptoms : Blinking and error F4 Cause : One of the indoor unit gas temperature thermistor reading abnormal. Action : Check CU error and indoor error using wire remote control. Check thermistor reading. Replace indoor gas temperature thermistor R3T. Test run . Method Of Error Detection In cooling operation detect the condition under which liquid refrigerant returns to the compressor according to the temperature and pressure of each part. Error Decision Conditions When the following"
YouTube Link 2022-03-12T04:02Z 35.4K followers, 42.8K engagements

"VRV [--] Tamil Auto-charge + Test run Brand : Daikin VRV [--] Auto charge + test run in Tamil. #bonmj #airconditioner #daikin"
YouTube Link 2026-02-14T16:01Z 35.4K followers, [----] engagements

"How to measure refrigerant pressure using monitor mode Daikin VRV4 Brand : Daikin VRV4 model : RXQ14TY1/ RXQ8TY1 Check refrigerant pressure using monitor mode. Mode 1- [--] 1)press Mode Button BS1 once 2)press Set Button BS2 [--] times (high pressure) or [--] times for (low pressure) 3)press BS3 once .to get the answer at [--] segment. 4)press BS1 once to exit. please subscribe my YouTube channel https://youtube.com/c/BonMj #bonmj #daikin #vrv4"
YouTube Link 2022-02-12T08:11Z 35.4K followers, 39.5K engagements

"Learn VRF air conditioner Dip Switch Setting Panasonic FSV-EX Installation Instruction Brand : PANASONIC FSV (VRF) Model : U-16ME2R8/U-12ME2R8 Action : New installation dip switch setting. #bonmj #airconditioner #panasonic"
YouTube Link 2025-04-27T04:19Z 35.4K followers, [----] engagements

"VRV air conditioner method for adding refrigerant RXQ _ _ AYMG Brand : Daikin R410a Model : RXQ12AYMG Auto charge and test run. #daikin #airconditioning #bonmj"
YouTube Link 2024-10-05T04:11Z 35.4K followers, 10.3K engagements

"How to by pass VRV [--] inverter compressor and main CU emergency settings Brand : Daikin Model : RXUQ20AYM Emergency settings #bonmj #daikin #airconditioning"
YouTube Link 2025-08-30T07:57Z 35.4K followers, [----] engagements

"Daikin VRV How to resolved error code PJ after replacing outdoor main PC Board. Brand : Daikin VRV [--] model : RXQ14PAY13 Error code: PJ / U3 1)Error PJ Outdoor unit: Faulty field setting after replacing main PCB or faulty combination of PCB. Method of Malfunction Detection The Malfunction is detected according to communications with the inverter. Malfunction Decision Conditions Make judgment according to communication data on whether or not the type of the inverter PCB is correct. Supposed Cause *Faulty (or not)field setting after replacing man PCB. 2)Error U3 Outdoor unit : Check operation"
YouTube Link 2022-04-16T06:39Z 35.4K followers, 32.1K engagements

"How to diagnosis and repair VRV-X air conditioner LC-14 LC-19 Daikin RXUQ _ AYM Brand : Daikin VRV-X A series Model : RXUQ _ AYM Error : LC-19 and LC-14 Cause : CU fan PCB faulty Action : replace fan Pcb #daikin #bonmj #airconditioning"
YouTube Link 2024-09-01T03:15Z 35.4K followers, 11.9K engagements

"Panasonic FSV How to increase ducted unit fan speed CZ-TRC4 CZ-TRC2 Brand : Panasonic FSV (VRF) remote control model : CZ-TRC2 CZ-TRC4 What is feild setting for to increase static pressure. 1)high ceiling cassette unit 2)long ducting How to set 1)press tools set and cancel button in the same time. display appear Code no [--] set data [----]. 2)press temperature down button to change to code no to bO(BO) display appear Code no bOset data [----]. 3)press clock up button to change the data no. to [----] (100Pa) (can set from [----] to35681112131415) 4)press Set button to confirm. 5)press Tools button to"
YouTube Link 2021-09-29T15:58Z 35.1K followers, 12.5K engagements

"How to troubleshoot common AC pressure sensor problem VRV - Daikin Brand : Daikin VRV3 Model : RXQ13PAY13 Error : E3 JA JC Cause : high pressure sensor faulty. One of the most common causes of pressure sensor failures is mechanical damage which can occur due to excessive vibration shock impact or wear and tear. Mechanical damage can affect the sensor's diaphragm housing wiring or connectors resulting in inaccurate readings signal loss or short circuits. #bonmj #airconditioning #daikin"
YouTube Link 2024-10-26T04:30Z 35K followers, [----] engagements

"Mini FSV Auto address & settings Panasonic air conditioner Thanks for watching my video please like share and subscribe . #bonmj #airconditioner #panasonic"
YouTube Link 2023-04-08T07:47Z 35.1K followers, [----] engagements

"AC refrigerant charging after replace compressor and eev R410a"
YouTube Link 2023-09-19T01:30Z 34.9K followers, [----] engagements

"Mitsubishi VRF How to rectify Error [----] [----] [----] [----] [----] Connection Kit Brand : Mitsubishi Electric vrf model : PUCY-P350YKA (CU) model : MSXY-FN13VE (FCU) Error : [----] [----] [----] [----] [----] #bonmj #airconditioner #mitsubishi"
YouTube Link 2022-12-03T09:08Z 34.7K followers, 16.9K engagements

"How to solve Error E2-01 VRV air conditioner Daikin Brand : Daikin Model : RXQ12AYM Error : E2-01 Cause : PCB short circuit by Lizard Action : switch off power supply and remove the Lizard body from Pcb component. #bonmj #daikin #airconditioner"
YouTube Link 2025-07-19T07:30Z 35.4K followers, [----] engagements

"VRV practice and discussion work and learning Air conditioner"
YouTube Link 2025-06-08T09:51Z 35.4K followers, [----] engagements

"DIP switch setting for new installation aircon Panasonic FSV VRF EX Brand : Panasonic FSV Thanks for watching my YouTube channel. please like share and subscribe. #bonmj #airconditioner #Panasonic"
YouTube Link 2023-01-14T09:04Z 35K followers, [----] engagements

"Why aircon not cooling Multi Split R32 Brand : Mitsubishi Electric multi split R32 Model : MXY-3H28VG Error : no error Symptoms: switch on one not cold on both ok. (System [--] only connected to [--] indoor) Fault : installer fault wire wring connection. #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-11-09T04:17Z 35.4K followers, [----] engagements

"How to solved air conditioner Error A9 Daikin VRV"
YouTube Link 2024-09-28T15:32Z 34.6K followers, [----] engagements

"Error [----] CU address setting Mitsubishi Electric VRF"
YouTube Link 2026-01-11T03:27Z 35.4K followers, [----] engagements

"Panasonic FSV T&C👍👍"
YouTube Link 2025-08-20T23:05Z 35.4K followers, [----] engagements

"How to Replace Indoor EEV with Heat Sink Paste Daikin VRV Brand : Daikin VRV3 type : Ducted model : FXMQ125PAVE Replace FCU Coil motorized vavle and body motorized vavle using Heat Sink Paste. *purging with Nitrogen before fix back the evaporator coil. #Daikin #VRV3 #VRV #VRV4"
YouTube Link 2021-05-26T16:33Z 34.9K followers, [----] engagements

"How to solve error 6607-SC Mitsubishi Electric VRF Error : [----] SC Cause : System remote controller no power supply and miss communication Model : System remote controller PAC-SF44SRA Model : Schedule Timer PAC-YT34STA Model : Power Supply Unit PAC-SC51KUA Thanks for watching my videos Please like share and subscribe #bonmj #airconditioner #mitsubishi"
YouTube Link 2024-06-22T06:24Z 34.4K followers, [----] engagements

"High floor troubleshooting-Daikin Multi split unit"
YouTube Link 2025-11-02T05:09Z 35.4K followers, [----] engagements

"Blown fuse PCB"
YouTube Link 2025-11-16T02:26Z 35.4K followers, [----] engagements

"How to solve City Multi air conditioner compressor unable load Troubleshooting Brand : Mitsubishi Electric City Multi Error : 6607/5101/5102/5103/5104 Cause : cu control Pcb and indoor TH22 faulty Action : replace control Pcb and indoor thermistor #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-10-20T05:20Z 35.4K followers, [----] engagements

"Daikin VRV [--] How to identify the specific fault error J7/8/9 Brand : Daikin VRV [--] Model : RXQ18PAY1 Error : J9 Cause : outdoor thermistor faulty Action : replaced thermistor #airconditioner #bonmj #daikin"
YouTube Link 2026-01-04T05:06Z 35.4K followers, [----] engagements

"7 segment Display Non Stop Flickering VRV [--] Daikin air conditioner [----] Brand : Daikin VRV4 Model : RXUQ8AYM Error : indoor error U4 outdoor no error and [--] segment non stop blinking Cause : inverter pcb faulty. #airconditioning #bonmj #daikin"
YouTube Link 2026-01-17T10:20Z 35.4K followers, [----] engagements

"VRF air conditioner troubleshooting Mitsubishi Electric error [----] Brand : Mitsubishi Electric VRF Error : [----] (052) Cause : CU TH2 faulty Action : replace TH2 and test run. #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-10-11T05:13Z 35.4K followers, [----] engagements

"Headache job of the day aircon power trip Model : RXUQ8AYM Error : power trip main switch Cause : short circuit by Lizard #bonmj #airconditioner #daikin"
YouTube Link 2025-12-11T05:02Z 35.4K followers, [----] engagements

"Daikin VRV ( Ceiling Suspended) EEV replacement Electronic Expansion Valve Brand : Daikin Fcu ceiling suspended Model : Error : no error but not cooling Cause : Coil motorized valve jammed (EEV) #bonmj #airconditioner #daikin"
YouTube Link 2023-09-02T07:31Z 34.7K followers, 23.2K engagements

"26 March [----] Panasonic FSV - Multi Outdoor Unit (4CU)"
YouTube Link 2025-03-26T01:54Z 35.4K followers, [----] engagements

"Daikin VRV Troubleshooting indoor and outdoor unit communication problem Error U4 Brand : Daikin VRV Model : RXQ12AYM/RXQ10AYM (CU) Model : FXMQ200MAVE (FCU) Error code : U4 Cause : indoor/outdoor unit communication problem. #bonmj #daikin #vrv"
YouTube Link 2022-04-30T06:01Z 35.3K followers, 41.3K engagements

"How VRV air conditioning installation work Tamil VRV air conditioning installation involves connecting a single outdoor unit to multiple indoor units via refrigerant piping allowing for zonal temperature control and individual comfort settings. Unlike traditional systems VRV eliminates the need for ductwork simplifying installation and offering flexibility in design. Here's a more detailed breakdown: [--]. System Components: Outdoor Unit: Contains the compressor fan and heat exchanger. Indoor Units: Each unit has a heat exchanger and fan to deliver conditioned air. Refrigerant Piping: Connects"
YouTube Link 2025-05-10T04:22Z 35.4K followers, 10.3K engagements

"Daikin How to solve error code U3 after replacing new main pcb VRVA Brand : Daikin model : RXQ16AYM Replace new main PCB. Important for Daikin VRV-A after replacing new PCB must conduct Auto Charge before test run. #daikin #bonmj #vrv4"
YouTube Link 2021-09-26T08:06Z 35.4K followers, 79.5K engagements

"Chilled water to normal ac package unit air conditioner Brand : National Modify from chilled water to normal ac. #bonmj #airconditioner #panasonic"
YouTube Link 2026-02-04T12:29Z 35.4K followers, [----] engagements

"Daikin VRV How to set wire remote control weekly timer. (BRC1E63) Daikin wire remote controller model : BRC1E63 weekly timer schedule setting. #Daikin #VRV #VRV3 #VRV4"
YouTube Link 2021-04-20T15:40Z 35.3K followers, 16.1K engagements

"VRV Air conditioner troubleshooting and repair E5 RXQ _ _ PAY Brand : Daikin VRV3 Model : RXQ10PAY ERROR : E5 Cause : inverter compressor unable to start Action : Replace inverter compressor and inverter PCB #airconditioner #daikin #bonmj"
YouTube Link 2024-08-24T04:10Z 35.4K followers, 10.3K engagements

"Daikin VRV4 Error F4-02"
YouTube Link 2025-02-03T08:14Z 35.3K followers, 15.4K engagements

"Daikin Air conditioner VRV4 Main components in the unit RXQ612 HP Parts reading Brand : Daikin VRV4 Model : RXQ6 to [--] AYNG #bonmj #airconditioning #daikin"
YouTube Link 2024-10-13T03:14Z 35.3K followers, [----] engagements

"Aircon error code differ from actual cause RZFC R32 Brand : Daikin R32 Model : RZFC140DY1G Error : indoor and outdoor U4 Cause : insufficient gas Action : charging gas and follow up check leak #bonmj #daikin #airconditioner"
YouTube Link 2026-02-01T07:12Z 35.4K followers, [----] engagements

"How to adjust Panasonic VRF system Dip switch settings no. Of indoor unit Brand : Panasonic Model : U - 18ME1H7 Error : E06 Cause : one of the indoor unit Pcb faulty Action : temporary solution cgange no of indoor unit #bonmj #airconditioner #panasonic"
YouTube Link 2025-08-09T06:12Z 35.4K followers, [----] engagements

"Aircon Enzyme Service ceiling cassette error P10 A3 [----] P05 etc. Brand : All brand Type : Ceiling cassette How important Enzyme Service : Environmental Friendlier #bonmj #Daikin #Mitsubishi"
YouTube Link 2023-12-09T06:35Z 22.3K followers, [---] engagements

"Daikin vrv4 replaced inverter pcb"
YouTube Link 2025-07-03T05:05Z 35.4K followers, [----] engagements

"New installation FSV"
YouTube Link 2024-08-18T07:44Z 31.3K followers, [----] engagements

"Mitsubishi Starmex How to unclog dirty evaporator coil. Brand: Mitsubishi Starmex type : wallmounted What happens if the evaporator coil is clogged An extremely dirty evaporator coil can cause your AC to breakdown completely. This is happens when condensation forms on the dirt and then freezes during the AC's operation. The buildup of frost stops the heat transfer with the air in your home which causes the air conditioner to stop cooling at all. Mitsubishi starMEX how to remove blower in-depth video: https://youtu.be/GXLTcSNI3v8 How to clean your Mitsubishi starmex aircon wallmounted:"
YouTube Link 2021-10-20T16:44Z 30K followers, 17.2K engagements

"How to activate Forced Operation mode VRV4 Forced start from outdoor To force-start a Daikin VRV4 system from outdoors you must first activate the Forced Operation mode not the Forced Fan mode which is for testing communication. Enter the service menu on the outdoor unit by holding the Mode button until H1P is solid then press the Set button five times to reach setting number [--]. Press Return to enter setting [--] then use the Set button to change the value to [--] (representing "On"). Press Return once to save the setting and then again to activate it which will show "TEST" on the remote display."
YouTube Link 2025-09-14T02:25Z 33.8K followers, [---] engagements

"Daikin inverter single split R410 aircon blinking error UO U4 Brand : Daikin inverter (single split) model : model : error : UO U4 UO : shortage of refrigerant in a closed stop valve or there is clogged refrigerant pipe in the system or may be a fault with the expansion valve. U4 : communication error between indoor and outdoor units/outdoor BS units. #bonmj #daikin #airconditioner"
YouTube Link 2022-07-23T09:00Z 31.2K followers, 65.2K engagements

"What to do when you dont detect aircon error Daikin inverter Brand : Daikin inverter Model : RKS25GVMG (CU) Symptoms : not cooling & no blinking outdoor not working. Error : no error Cause : Outdoor EEV coil faulty Action : replaced new EEV Thanks for watching ❤❤ Please Subscribe Like and share. ❤❤❤🥰🥰🙏🙏 #bonmj #airconditioning #hvac"
YouTube Link 2024-11-30T04:30Z 31.2K followers, [----] engagements

"Air conditioner troubleshooting and repair high pressure switch and fan motor Daikin 20HP Brand : Daikin R22 non inverter Model : RU- [--] Error : no error Cause : not cold compressor cut off often high pressure switch open due to fan motor jammed. Action : replace fan motor and fan blade. #bonmj #airconditioner #daikin"
YouTube Link 2025-07-06T05:39Z 35.4K followers, [----] engagements

"0 psi VRV4 - RQQ D checker & manifold gauge "
YouTube Link 2023-07-11T06:49Z 31.1K followers, [----] engagements

"How to solve air conditioner indoor unit not working RZR _ Inverter ac Brand : Daikin inverter R410 Model : RZR125MVMG Error : no error Cause : indoor unable to switch on due to no power supply from outdoor. Action : check and found F4U (6.3A)blow replace fuse. #bonmj #airconditioner #daikin"
YouTube Link 2025-06-28T05:14Z 35.4K followers, [----] engagements

"Mitsubishi VRF ceiling cassette error [----] aircon blinking Brand : Mitsubishi Electric VRF model : PLFY-P125VBM-E Error code : [----] and [----] Error [----] Check MA wire remote control Error [----] Check drain pump and float switch #bonmj #mitsubishi #VRF"
YouTube Link 2022-06-18T09:18Z 31.4K followers, [----] engagements

"Mitsubishi starMEX aircon green light keep blinking MSXY-FN10_18VE Brand : Mitsubishi Electric inverter (starMEX) model : MSXY-FN10VE to MSXY-FN18VE error : no error symptoms : [--] operation light keep blinking cause : louver never fix properly. #bonmj #mitsubishi #airconditioner"
YouTube Link 2022-12-17T09:02Z 33.7K followers, 79.7K engagements

"How to replace CU Fan & Inverter PCB RXUQ_AYM VRV4 Brand : Daikin VRV [--] Model : RXUQ20AYM Error : LC Cause :PCB faulty Action : Replace fan & inverter pcb #bonmj #airconditioning #daikin"
YouTube Link 2025-08-24T04:10Z 35.4K followers, [----] engagements

"VRV [--] How to solve Reiri control not functioning air conditioner Brand : Daikin VRV [--] Model : RXQ12AYM Error : LC-14 Cause : inverter pcb faulty due to short circuit by Lizard. (Main cu error LC-14 and inverter pcb short circuit by Lizard and this cu is connected with Reiri control and the Reiri control become not functioning well) #bonmj #airconditioner #daikin"
YouTube Link 2025-03-01T07:00Z 30.8K followers, [---] engagements

"Daikin inverter error code F3 Brand : Daikin inverter model : RKS25GVMG (CU) model : FTKS25DVM(Wallmouted) error code : F3 fault : Condenser coil choke by dust. solutions : wash Condensing unit. #Daikin #VRV3 #VRV #VRV4"
YouTube Link 2021-04-09T23:20Z 31.2K followers, 102.8K engagements

"HVAC How to solve Error J2 VRV3 Brand : Daikin VRV [--] Model : RXQ18PAY1 Error : J2 Cause : machine old age since [----] Action : suggest replace new aircon #bonmj #daikin #airconditioner"
YouTube Link 2025-03-15T08:00Z 35.4K followers, [----] engagements

"Air conditioner troubleshooting under hot sun"
YouTube Link 2025-09-07T01:18Z 35.4K followers, [----] engagements

"VRF gas leak 👷👷#bonmj #airconditioner #airconditioning VRF first time attend has leak issues. #bonmj #airconditioner #airconditioning"
YouTube Link 2025-10-02T03:18Z 35.4K followers, [----] engagements

"Mitsubishi Electric VRF troubleshooting.#bonmj #airconditioner #airconditioning"
YouTube Link 2025-09-22T03:21Z 35.4K followers, [----] engagements

"How to solve Error E9-04 RQQ-TYM Daikin VRV [--] Brand : Daikin Model : RQQ12TYM Error : indoor E9 outdoor E9-04 Symptoms : all indoor unit are blinking and not cooling outdoor not working. Cause : EEV coil Y1E (main) faulty #bonmj #airconditioner #daikin"
YouTube Link 2023-11-04T06:40Z 21.7K followers, [----] engagements

"How to activate Forced Operation mode VRV4 #bonmj #daikin #airconditioner"
YouTube Link 2025-09-14T05:58Z 35.4K followers, [----] engagements

"Time to clean Filter aircon"
YouTube Link 2025-05-31T04:37Z 35.4K followers, [----] engagements

"How to solved Error A5 & UH Daikin R32 multi split Brand : Daikin R32 multi split Model : Error code : A5 & UH Cause : communication cable wrong connection Please like and share and subscribe my YouTube channel. Thanks for watching and your support.❤❤🩷🩷"
YouTube Link 2024-05-25T07:20Z 25.8K followers, [----] engagements

"How to check Motorized Valve Coil reading Daikin inverter Brand : Daikin inverter (multi split) model : 3MKS50ESG (CU) Error : A5 symptoms : There were icing on the evaporator coil aircon was switched on. Cause : CU EEV or parts name is Motorized Valve Coil faulty Good condition Motorized valve coil reading is around [--] ohm. please Subscribe my YouTube channel. https://youtube.com/c/BonMj #bonmj #daikin #airconditioner"
YouTube Link 2022-02-26T14:48Z 31.2K followers, 40.4K engagements

"One of the reason why your aircon top up gas very often AC gas leak R410 R32 Brand : Any brand Symptoms : not cold Cause : gas leak #bonmj #airconditioner #daikin"
YouTube Link 2024-03-23T06:39Z 29.2K followers, [----] engagements

"How to clear system control filter alarm #bonmj Mitsubishi Electric VRF"
YouTube Link 2025-04-03T11:59Z 35.4K followers, [----] engagements

"VRF troubleshooting fuse blows"
YouTube Link 2025-05-18T01:55Z 35.4K followers, [----] engagements

"How to solve Fujitsu air conditioner blinking (10 times & [--] times) Airstage R32 #bonmj Brand : Fujitsu inverter R32 Error : operation light [--] times Timer light [--] times (Error 35) Cause : insufficient gas(for this case) #bonmj #ac #airconditioning"
YouTube Link 2024-12-28T04:01Z 30K followers, [---] engagements

"To rectify an SPL error on an air conditioner Daikin single split Brand : Daikin inverter R410a single split Error : U4 Cause : Outdoor Pcb faulty #bonmj #airconditioning #daikin"
YouTube Link 2025-04-12T05:58Z 35.4K followers, [----] engagements

"The easiest ways to check for a gas leak.#bonmj #airconditioning #airconditioner"
YouTube Link 2025-09-16T03:57Z 35.4K followers, [----] engagements

"2025 New Launch Model Panasonic split aircon Easy servicing Brand : Panasonic Model : CU-2/3/4U20/28-33/38YBZ(CU multi split) Model : CS-XU - BKZW #bonmj #airconditioner #panasonic"
YouTube Link 2025-06-22T04:18Z 35.4K followers, [----] engagements

"Why did my Midea aircon suddenly stop working error E5 Brand : Midea Multi split Model : M30A-21CDN1-QC4 Error : E5 Cause : Outdoor CU fan capacitor reading drop. Action : replaced cu fan capacitor. #bonmj #hvac #midea"
YouTube Link 2025-04-05T05:16Z 35.4K followers, [----] engagements

"How to Lock Temperature setting Mitsubishi Electric wire remote controller PAR-40/41 MAA #bonmj"
YouTube Link 2025-07-26T03:37Z 35.4K followers, [----] engagements

"Why aircon status light blinking [--] or [--] times Mitsubishi starmex Multi-split Thanks for watching my YouTube channel. #bonmj #airconditioner #starmex"
YouTube Link 2023-10-23T21:20Z 21.5K followers, 15.5K engagements

"How to merging two different brand VRF air conditioners HVAC Brand : Sanyo VRF / Panasonic VRF Aircon replacement. Terima kasih kerana anda sudi menonton video Saya. #bonmj #airconditioner #panasonic"
YouTube Link 2025-09-28T04:19Z 35.4K followers, [----] engagements

"Daikin VRV3 How to rectify error code U1 Brand : Daikin VRV [--] model : RXQ14PAY13 error code : U1 #daikin #vrv3 #bonmj"
YouTube Link 2021-09-16T16:12Z 33.3K followers, 17.1K engagements

"Error L5-03 VRV4 air conditioner troubleshooting Brand : Daikin VRV4 Model : RXUQ12AYM Error : L5-03 Cause : Compressor lock #bonmj #airconditioning #daikin"
YouTube Link 2025-07-12T06:15Z 35.4K followers, [----] engagements

"How to check grounded VRV compressor Daikin VRV3 Error L1 Brand : Daikin VRV [--] model : RXQ16PAY13 Symptoms: Trip RCCB error L1 #bonmj #airconditioner #daikin"
YouTube Link 2023-01-21T09:30Z 32.6K followers, 14.8K engagements

"How do you troubleshoot an aircon LEV valve Mitsubishi VRF Brand : Mitsubishi Electric model : PDFY-P100VM-E (FCU-Ducted) Error code : no error. Complaint : aircon not cooling Symptoms : One of the FCU LEV fully open CU TH [--] reading very low. Cause : LEV faulty #bonmj #mitsubishi #vrf"
YouTube Link 2022-03-05T12:57Z 29.1K followers, 14.9K engagements

"Why my aircon compressor fail to start low pressure"
YouTube Link 2025-03-22T09:46Z 35.4K followers, [----] engagements

"How to solve error L4 Inverter Heatsink Daikin Super inverter Brand : Daikin Super inverter R410a Model : RZR125MVMG Error : L4 Cause : Inverter pcb never fix properly screw missing and never apply compound by contractor. Action : apply heatsink compound and retighten heatsink cover. #bonmj #airconditioning #daikin"
YouTube Link 2024-09-22T02:23Z 29.1K followers, [----] engagements

"Mistake in air conditioner (AC) installation Wrong Configuration Brand : Mitsubishi Electric VRF Model : PUHY-P450 (existing model) PUCY-P200&250 (new model) Error : [----] Cause : CU wrong configuration Action : the best solution is cut one of the cu and re run new piping and separate to [--] system. #bonmj #airconditioner #airconditioning"
YouTube Link 2025-10-04T04:03Z 35.4K followers, [----] engagements

"Daikin error code L1 How to fault finding. Brand : Daikin inverter model : RZR50LUV1 Error code : L1 L1 is a outdoor PCb failure.There may be an underlying cause forthe failure so many also be a fan motor or compressor failure that caused the problem. 1)Reset power supply and test run . 2)check outdoor fan motor or compressor 3)if outdoor fan motor ok or compressor not running please check the compressor incoming voltage. https://youtu.be/T-6gHK3iuTM https://youtu.be/ug03QxjwGyA https://youtu.be/_RJ1CKuF_q8 https://youtu.be/x--ISSQVd-Y https://youtu.be/qUkB6Jq1t9Q https://youtu.be/aC_gN3FzNGU"
YouTube Link 2023-10-27T12:38Z 21.6K followers, 28.4K engagements

"Daikin inverter air conditioner Thermistor Failure Symptom Brand : Daikin model : MKS80QVM ERROR : No error Symptom: Running after 45minutesFcu auto off and auto on backoutdoor LED [--] & [--] light up. Cause : Thermistor failure Symptomthermistor short circuit. #bonmj #daikin #inverter"
YouTube Link 2021-12-25T05:09Z 31.2K followers, 28.4K engagements

"How to solve Mitsubishi Heavy Industries (MHI) aircon indoor unit blinking error code Brand : Mitsubishi Heavy Industries (inverter) Model : SCM60ZJ-S1 (multi split) Error : Indoor Run light On Timer light one time flash. Cause : Compressor not functioning well. #bonmj #airconditioningrepair #airconditioner"
YouTube Link 2024-06-09T05:06Z 31.2K followers, [----] engagements

"VRV [--] Tamil Auto-charge + Test run Brand : Daikin VRV [--] Auto charge + test run in Tamil. #bonmj #airconditioner #daikin"
YouTube Link 2026-02-14T16:01Z 35.4K followers, [----] engagements

"Chilled water to normal ac package unit air conditioner Brand : National Modify from chilled water to normal ac. #bonmj #airconditioner #panasonic"
YouTube Link 2026-02-04T12:29Z 35.4K followers, [----] engagements

"Aircon error code differ from actual cause RZFC R32 Brand : Daikin R32 Model : RZFC140DY1G Error : indoor and outdoor U4 Cause : insufficient gas Action : charging gas and follow up check leak #bonmj #daikin #airconditioner"
YouTube Link 2026-02-01T07:12Z 35.4K followers, [----] engagements

"Midnight job aircon hoisting VRF air conditioner replacement #bonmj #airconditioner #panasonic"
YouTube Link 2026-01-25T04:37Z 35.4K followers, [----] engagements

"VRF installation work in progress 👍"
YouTube Link 2026-01-22T03:03Z 35.4K followers, [----] engagements

"7 segment Display Non Stop Flickering VRV [--] Daikin air conditioner [----] Brand : Daikin VRV4 Model : RXUQ8AYM Error : indoor error U4 outdoor no error and [--] segment non stop blinking Cause : inverter pcb faulty. #airconditioning #bonmj #daikin"
YouTube Link 2026-01-17T10:20Z 35.4K followers, [----] engagements

"Error [----] CU address setting Mitsubishi Electric VRF"
YouTube Link 2026-01-11T03:27Z 35.4K followers, [----] engagements

"Daikin VRV [--] How to identify the specific fault error J7/8/9 Brand : Daikin VRV [--] Model : RXQ18PAY1 Error : J9 Cause : outdoor thermistor faulty Action : replaced thermistor #airconditioner #bonmj #daikin"
YouTube Link 2026-01-04T05:06Z 35.4K followers, [----] engagements

"Daikin VRV [--] Malfunction Code List Brand : Daikin VRV [--] #bonmj #airconditioner #daikin"
YouTube Link 2025-12-28T07:09Z 35.4K followers, [----] engagements

"Daikin VRV6 Automatic refrigerant charge WITH test run procedure 2-3=2* Brand : Daikin VRV [--] Model : RXUQ8B Automatic charge and test run precedure #bonmj #airconditioner #daikin"
YouTube Link 2025-12-13T12:22Z 35.4K followers, [----] engagements

"Headache job of the day aircon power trip Model : RXUQ8AYM Error : power trip main switch Cause : short circuit by Lizard #bonmj #airconditioner #daikin"
YouTube Link 2025-12-11T05:02Z 35.4K followers, [----] engagements

"Compare old and new leak detector"
YouTube Link 2025-11-30T10:59Z 35.4K followers, [----] engagements

"How to solve Midea air conditioner error EL-01 Model : MSEOD-18 Error : EL-01 Cause : communication issues Action : reset system (off power supply and on back) Midea AC error EL-OC R32 Single split https://youtu.be/s73fWcSuXYc #bonmj #airconditioner #midea"
YouTube Link 2025-11-23T06:21Z 35.4K followers, [----] engagements

"Blown fuse PCB"
YouTube Link 2025-11-16T02:26Z 35.4K followers, [----] engagements

"Why aircon not cooling Multi Split R32 Brand : Mitsubishi Electric multi split R32 Model : MXY-3H28VG Error : no error Symptoms: switch on one not cold on both ok. (System [--] only connected to [--] indoor) Fault : installer fault wire wring connection. #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-11-09T04:17Z 35.4K followers, [----] engagements

"High floor troubleshooting-Daikin Multi split unit"
YouTube Link 2025-11-02T05:09Z 35.4K followers, [----] engagements

"How to solve City Multi air conditioner compressor unable load Troubleshooting Brand : Mitsubishi Electric City Multi Error : 6607/5101/5102/5103/5104 Cause : cu control Pcb and indoor TH22 faulty Action : replace control Pcb and indoor thermistor #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-10-20T05:20Z 35.4K followers, [----] engagements

"VRF air conditioner troubleshooting Mitsubishi Electric error [----] Brand : Mitsubishi Electric VRF Error : [----] (052) Cause : CU TH2 faulty Action : replace TH2 and test run. #bonmj #airconditioner #mitsubishi"
YouTube Link 2025-10-11T05:13Z 35.4K followers, [----] engagements

"Mistake in air conditioner (AC) installation Wrong Configuration Brand : Mitsubishi Electric VRF Model : PUHY-P450 (existing model) PUCY-P200&250 (new model) Error : [----] Cause : CU wrong configuration Action : the best solution is cut one of the cu and re run new piping and separate to [--] system. #bonmj #airconditioner #airconditioning"
YouTube Link 2025-10-04T04:03Z 35.4K followers, [----] engagements

"VRF gas leak 👷👷#bonmj #airconditioner #airconditioning VRF first time attend has leak issues. #bonmj #airconditioner #airconditioning"
YouTube Link 2025-10-02T03:18Z 35.4K followers, [----] engagements

"How to merging two different brand VRF air conditioners HVAC Brand : Sanyo VRF / Panasonic VRF Aircon replacement. Terima kasih kerana anda sudi menonton video Saya. #bonmj #airconditioner #panasonic"
YouTube Link 2025-09-28T04:19Z 35.4K followers, [----] engagements

"Mitsubishi Electric VRF troubleshooting.#bonmj #airconditioner #airconditioning"
YouTube Link 2025-09-22T03:21Z 35.4K followers, [----] engagements

"The easiest ways to check for a gas leak.#bonmj #airconditioning #airconditioner"
YouTube Link 2025-09-16T03:57Z 35.4K followers, [----] engagements

"How to activate Forced Operation mode VRV4 #bonmj #daikin #airconditioner"
YouTube Link 2025-09-14T05:58Z 35.4K followers, [----] engagements

"Air conditioner troubleshooting under hot sun"
YouTube Link 2025-09-07T01:18Z 35.4K followers, [----] engagements

"How to by pass VRV [--] inverter compressor and main CU emergency settings Brand : Daikin Model : RXUQ20AYM Emergency settings #bonmj #daikin #airconditioning"
YouTube Link 2025-08-30T07:57Z 35.4K followers, [----] engagements

"How to replace CU Fan & Inverter PCB RXUQ_AYM VRV4 Brand : Daikin VRV [--] Model : RXUQ20AYM Error : LC Cause :PCB faulty Action : Replace fan & inverter pcb #bonmj #airconditioning #daikin"
YouTube Link 2025-08-24T04:10Z 35.4K followers, [----] engagements

"Panasonic FSV T&C👍👍"
YouTube Link 2025-08-20T23:05Z 35.4K followers, [----] engagements

"How to adjust Panasonic VRF system Dip switch settings no. Of indoor unit Brand : Panasonic Model : U - 18ME1H7 Error : E06 Cause : one of the indoor unit Pcb faulty Action : temporary solution cgange no of indoor unit #bonmj #airconditioner #panasonic"
YouTube Link 2025-08-09T06:12Z 35.4K followers, [----] engagements

"How to Lock Temperature setting Mitsubishi Electric wire remote controller PAR-40/41 MAA #bonmj"
YouTube Link 2025-07-26T03:37Z 35.4K followers, [----] engagements

"How to solve Error E2-01 VRV air conditioner Daikin Brand : Daikin Model : RXQ12AYM Error : E2-01 Cause : PCB short circuit by Lizard Action : switch off power supply and remove the Lizard body from Pcb component. #bonmj #daikin #airconditioner"
YouTube Link 2025-07-19T07:30Z 35.4K followers, [----] engagements

"Error L5-03 VRV4 air conditioner troubleshooting Brand : Daikin VRV4 Model : RXUQ12AYM Error : L5-03 Cause : Compressor lock #bonmj #airconditioning #daikin"
YouTube Link 2025-07-12T06:15Z 35.4K followers, [----] engagements

"Air conditioner troubleshooting and repair high pressure switch and fan motor Daikin 20HP Brand : Daikin R22 non inverter Model : RU- [--] Error : no error Cause : not cold compressor cut off often high pressure switch open due to fan motor jammed. Action : replace fan motor and fan blade. #bonmj #airconditioner #daikin"
YouTube Link 2025-07-06T05:39Z 35.4K followers, [----] engagements

"Daikin vrv4 replaced inverter pcb"
YouTube Link 2025-07-03T05:05Z 35.4K followers, [----] engagements

"How to solve air conditioner indoor unit not working RZR _ Inverter ac Brand : Daikin inverter R410 Model : RZR125MVMG Error : no error Cause : indoor unable to switch on due to no power supply from outdoor. Action : check and found F4U (6.3A)blow replace fuse. #bonmj #airconditioner #daikin"
YouTube Link 2025-06-28T05:14Z 35.4K followers, [----] engagements

"2025 New Launch Model Panasonic split aircon Easy servicing Brand : Panasonic Model : CU-2/3/4U20/28-33/38YBZ(CU multi split) Model : CS-XU - BKZW #bonmj #airconditioner #panasonic"
YouTube Link 2025-06-22T04:18Z 35.4K followers, [----] engagements

"Test run after install new FCU"
YouTube Link 2025-06-22T02:02Z 35.4K followers, [----] engagements

"VRV practice and discussion work and learning Air conditioner"
YouTube Link 2025-06-08T09:51Z 35.4K followers, [----] engagements

"Time to clean Filter aircon"
YouTube Link 2025-05-31T04:37Z 35.4K followers, [----] engagements

"Why my aircon water leaking #bonmj #airconditioning #airconditioner"
YouTube Link 2025-05-24T01:41Z 35.4K followers, [----] engagements

"VRF troubleshooting fuse blows"
YouTube Link 2025-05-18T01:55Z 35.4K followers, [----] engagements

"How VRV air conditioning installation work Tamil VRV air conditioning installation involves connecting a single outdoor unit to multiple indoor units via refrigerant piping allowing for zonal temperature control and individual comfort settings. Unlike traditional systems VRV eliminates the need for ductwork simplifying installation and offering flexibility in design. Here's a more detailed breakdown: [--]. System Components: Outdoor Unit: Contains the compressor fan and heat exchanger. Indoor Units: Each unit has a heat exchanger and fan to deliver conditioned air. Refrigerant Piping: Connects"
YouTube Link 2025-05-10T04:22Z 35.4K followers, 10.3K engagements

"Learn VRF air conditioner Dip Switch Setting Panasonic FSV-EX Installation Instruction Brand : PANASONIC FSV (VRF) Model : U-16ME2R8/U-12ME2R8 Action : New installation dip switch setting. #bonmj #airconditioner #panasonic"
YouTube Link 2025-04-27T04:19Z 35.4K followers, [----] engagements

"To rectify an SPL error on an air conditioner Daikin single split Brand : Daikin inverter R410a single split Error : U4 Cause : Outdoor Pcb faulty #bonmj #airconditioning #daikin"
YouTube Link 2025-04-12T05:58Z 35.4K followers, [----] engagements

"Why did my Midea aircon suddenly stop working error E5 Brand : Midea Multi split Model : M30A-21CDN1-QC4 Error : E5 Cause : Outdoor CU fan capacitor reading drop. Action : replaced cu fan capacitor. #bonmj #hvac #midea"
YouTube Link 2025-04-05T05:16Z 35.4K followers, [----] engagements

"How to clear system control filter alarm #bonmj Mitsubishi Electric VRF"
YouTube Link 2025-04-03T11:59Z 35.4K followers, [----] engagements

"26 March [----] Panasonic FSV - Multi Outdoor Unit (4CU)"
YouTube Link 2025-03-26T01:54Z 35.4K followers, [----] engagements

"Why my aircon compressor fail to start low pressure"
YouTube Link 2025-03-22T09:46Z 35.4K followers, [----] engagements

"HVAC How to solve Error J2 VRV3 Brand : Daikin VRV [--] Model : RXQ18PAY1 Error : J2 Cause : machine old age since [----] Action : suggest replace new aircon #bonmj #daikin #airconditioner"
YouTube Link 2025-03-15T08:00Z 35.4K followers, [----] engagements

"All you need to know about Test run Daikin VRV4 Brand : Daikin VRV [--] Model : RXQ20AYM Testing and commissioning #bonmj #airconditioner #daikin"
YouTube Link 2025-03-08T06:12Z 35.4K followers, [----] engagements

Limited data mode. Full metrics available with subscription: lunarcrush.com/pricing